Appendix
Control
Mode
•
Single set point, non-ramping.
l
Single input, dual outputs.
l
Control outputs: User selectable as: Heat, Heat/Heat, Heat/Cool, Cool,
Cool/Cool, Heat/Alarm, Cool/Alarm
l
Outputs independent, or related via
deadband
for Heat/Cool.
l
ON/OFF:
3°F
or
1
.7°C
switching hysteresis or
0.3°F
or
0.l7°C
for
0.10 Units
.
l
PID
parameters:
Proportional band: 0 to
999°F/0
to
555°C(3
digit only)
0 to
999°F/0
to
555°C
or 0 to
99.9°F/0
to
55.5°C
(3 or 4 digit)
Reset: 0.00 to 9.99 repeats per minute.
Rate: 0.00 to 9.99 minutes.
Cycle time: 1 to 60 seconds.
l
Deadband:
±99°F,
±99
units or
±55°C
±9.9°F,
±9.9
units or
±5.5°C
for 0.1 decimal units)
Operator Interface
l
Membrane front panel.
l
Three or four digit 0.3”
(8mm)
LED diiplays.
l
MODE, AUTO/MANUAL, UP, and DOWN keys.
l
Dual digital displays.
Input
Thermocouple,
RTD,
and electrical process input.
Automatic cold junction compensation for thermocouple.
RTD input 2 or 3 wire, platinum, 100 ohm
@
0°C
user selectable, calibrate
to JIS curve #3916 (0.003916(0.003916ohm/ohm/°C or DIN curve #3850(0.003850ohm/ohm°C
Sensor break protection de-energizes control output to protect system or
selectable
bumpless
transfer to manual operation.
Grounded or ungrounded sensors.
°F/°C
or process variable units are user selectable.
Operating ranges user selectable.
J t/c:
32 to
999°F
or 0 to
750°C
(3 Digit)
32 to
1382°F
or 0 to
750°C
(4 Digit)
K t/c:
-328 to
2282°F
or -200 to
1250°C
T
t/c:
-328 to
662°F
or -200 to
350°C
N t/c:
32 to
2282°F
or 0 to
1250°C
PT 2
(Platinel2)
32 to
2543°F
or 0 to
1395°C
1°
RTD:
-328 to
1112°F
or -200 to
600°C
0.1°
RTD:
-99.9 to
392.0°F
or -99.9 to
200.0°C
0-5VDC:
-500 to 3500 units
4-20mA:
-500 to 3500 units
34