Series D8 User’s Guide Chapter 4: Operation and Setup
Doc. 0600-3120-2000 Watlow Anafaze 99
Figure 4.8 Application Using Process
Variable Retransmit
Table 4.8 shows the parameter setup for this example.
Table 4.8 Parameters Settings for Process
Variable Retransmit Example
Menu Parameter Value Comment
PV retrans
Ht output
retrans
PV 1
Choose to retransmit the loop 1 process variable.
PV retrans
Ht retrans
LowPV
0˚F
This is the input value represented by a 0 percent
output signal. The recorder input is a linear 4 to 20
mA signal representing a range of 0° F to 1000° F,
so we will use a 0 percent output signal to represent
0° F.
PV retrans
Ht retrans
HighPV
1000˚F
This is the input value represented by a 100 percent
output signal. The recorder input is a linear 4 to 20
mA signal representing a range of 0° F to 1000° F,
so we will use a 100 percent output signal to repre-
sent 1000° F.
PV retrans
Cl output
retrans
none
Not using the cool output of loop 2 to retransmit a
process variable.
D8
Furnace
Power
Controller
To Data
Logger
Loop 1 PID Output
Loop 2 PID Output
Heater
Loop 1
Input
Process
Variable
Serial
DAC